CVE-2024-27771
Executive Summary
CVE-2024-27771 is a critical path traversal vulnerability (CWE-22) affecting Unitronics Unistream Unilogic versions prior to 1.35.227. This flaw allows an unauthenticated attacker to traverse directories on the target system, potentially leading to remote code execution (RCE). With a CVSS score of 8.8, the vulnerability is highly exploitable over the network without requiring authentication or user interaction. The vendor has not released a public patch, and no proof-of-concept (PoC) code is currently available in public exploit databases. The EPSS score is 0.0%, indicating low exploitation activity in the wild, but the severity warrants immediate attention for organizations using affected versions.
This record — and 170,000+ others — are available via the ValtersIT API. One endpoint replaces five: NVD + GitHub CVE + CISA KEV + EPSS + Nuclei + Exploit-DB, unified.
No signup required
Supply Chain & Package Security
This vulnerability is not related to NPM, PyPI, Go, or Ruby ecosystems. It affects proprietary industrial control system (ICS) firmware from Unitronics.
CVSS Breakdown & Threat Level
- CVSS Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- Base Score: 8.8 (High)
- Attack Vector: Network (AV:N) – Exploitable remotely.
- Attack Complexity: Low (AC:L) – No special conditions required.
- Privileges Required: None (PR:N) – No authentication needed.
- User Interaction: None (UI:N) – No user action required.
- Scope: Unchanged (S:U) – Impact confined to the vulnerable component.
- Confidentiality Impact: High (C:H) – Full file system read access.
- Integrity Impact: High (I:H) – Potential to modify files or execute code.
- Availability Impact: High (A:H) – Could lead to denial of service or system compromise.
Threat Level: Critical. The combination of network exploitability, no authentication, and potential for RCE makes this a high-priority vulnerability for ICS/SCADA environments.
Deep Dive & Mechanics
The vulnerability resides in the Unilogic runtime of Unitronics Unistream PLCs. The software fails to properly sanitize user-supplied input when handling file paths, allowing an attacker to use path traversal sequences (e.g., ../) to escape the intended directory. This can lead to reading arbitrary files on the device, including sensitive configuration files, credentials, or system binaries. In the worst case, an attacker could upload a malicious file (e.g., a modified firmware or script) to achieve remote code execution.
Attack Flow:
- An attacker sends a crafted HTTP or proprietary protocol request to the Unistream device (typically on port 20256).
- The request includes path traversal sequences in a file path parameter (e.g.,
../../../etc/passwd). - The Unilogic runtime processes the request without validation, returning the contents of the traversed file.
- If the attacker can write files (e.g., via a similar traversal in a write operation), they can upload a malicious payload and execute it.
Root Cause: Lack of input validation and missing canonicalization of file paths in the Unilogic firmware.
Vulnerable vs. Patched Code
Vulnerable Code (Conceptual):
// Unilogic firmware < 1.35.227
void handle_file_request(char *user_path) {
char full_path[256];
sprintf(full_path, "/data/files/%s", user_path); // No sanitization
FILE *f = fopen(full_path, "r");
if (f) {
// Send file contents to client
}
}
Patched Code (Conceptual):
// Unilogic firmware >= 1.35.227
void handle_file_request(char *user_path) {
char full_path[256];
// Canonicalize and validate path
if (strstr(user_path, "..") != NULL || strchr(user_path, '/') != NULL) {
// Reject request
return;
}
snprintf(full_path, sizeof(full_path), "/data/files/%s", user_path);
FILE *f = fopen(full_path, "r");
if (f) {
// Send file contents to client
}
}
Note: The actual patch may involve additional checks, such as whitelisting allowed directories or using secure path resolution functions.
Exploitation & Lab Setup
Red Team (Offensive)
Prerequisites:
- Unitronics Unistream device with Unilogic < 1.35.227.
- Network access to the device (port 20256 typically).
- No authentication required.
Exploitation Steps:
- Scan for vulnerable devices: Use Shodan or Nmap to find Unitronics Unistream devices.
nmap -p 20256 --script banner <target_ip> - Craft path traversal request: Send a request to read
/etc/passwd(if Linux-based) or other sensitive files.curl "http://<target_ip>:20256/../../../etc/passwd" - Attempt RCE: If the device allows file uploads via path traversal, upload a malicious script.
# Example: Upload a reverse shell script curl -X POST -F "file=@shell.sh" "http://<target_ip>:20256/../../../tmp/shell.sh" - Execute the uploaded file: Trigger execution via another endpoint or by overwriting a startup script.
Note: No public exploit code is available; the above is conceptual.
Blue Team (Defensive)
Detection:
- Monitor network traffic for path traversal patterns (e.g.,
../,%2e%2e/). - Look for unusual file access requests to sensitive system files.
- Use the detection rules provided in the Detection Engineering section.
Honeypot Setup:
- Deploy a honeypot mimicking Unitronics Unistream to capture attacker behavior.
- Log all requests to port 20256 and analyze for traversal attempts.
Mitigation:
- Immediately upgrade to Unilogic version 1.35.227 or later.
- If patching is not possible, restrict network access to the device using firewalls or VPNs.
- Disable unnecessary services and change default credentials.
Indicators of Compromise (IOCs)
Network IOCs:
- HTTP requests containing
../or%2e%2e/in the URI path. - Connections to port 20256 from unexpected external IPs.
- Unusual file read requests (e.g.,
/etc/passwd,/etc/shadow,C:\Windows\System32\config\SAM).
- HTTP requests containing
File System IOCs:
- Presence of unexpected files in
/tmp,/data/files, or other writable directories. - Modified system binaries or configuration files.
- Presence of unexpected files in
Log IOCs:
- Unilogic logs showing failed path validation attempts (if logging is enabled).
- Repeated access to non-standard file paths.
Detection Engineering
YARA Rule
rule CVE_2024_27771_Path_Traversal {
meta:
description = "Detects path traversal attempts targeting Unitronics Unistream Unilogic"
author = "Valters IT"
date = "2024-10-01"
reference = "CVE-2024-27771"
strings:
$traversal1 = "../"
$traversal2 = "..\\"
$traversal3 = "%2e%2e/"
$traversal4 = "%2e%2e\\"
$sensitive1 = "/etc/passwd"
$sensitive2 = "/etc/shadow"
$sensitive3 = "boot.ini"
$sensitive4 = "windows\\system32"
condition:
any of ($traversal*) and any of ($sensitive*)
}
Sigma Rule
title: CVE-2024-27771 Path Traversal Attempt on Unitronics Unistream
id: 8a9b7c6d-5e4f-3a2b-1c0d-9e8f7a6b5c4d
status: experimental
description: Detects HTTP requests with path traversal patterns targeting Unitronics Unistream devices
author: Valters IT
date: 2024-10-01
logsource:
category: webserver
product: apache
service: access
detection:
selection:
cs-uri-query|contains:
- '../'
- '..\\'
- '%2e%2e/'
- '%2e%2e\\'
condition: selection
falsepositives:
- Legitimate use of '..' in some applications (rare)
level: high
Suricata Rule
alert http any any -> any 20256 (msg:"CVE-2024-27771 Path Traversal Attempt on Unitronics Unistream"; flow:to_server,established; content:"../"; http_uri; nocase; content:"/etc/passwd"; http_uri; nocase; sid:1000001; rev:1;)
Remediation & Mitigation
- Immediate Action: Upgrade Unilogic firmware to version 1.35.227 or later. Contact Unitronics support for patch availability.
- Network Segmentation: Isolate Unitronics devices on a separate VLAN with strict firewall rules. Do not expose them directly to the internet.
- Access Control: Implement strong authentication and disable default accounts. Use VPNs for remote access.
- Monitoring: Deploy the detection rules above to monitor for exploitation attempts.
- Backup: Regularly backup device configurations and firmware to enable recovery.
- Vendor Communication: Monitor Unitronics security advisories for updates.